Following a no-heat problem through a Wallingford electric air handler
Heat was not circulating through this Wallingford home. Testing at the electric air handler found a failed internal relay that was not passing power to the fan when heating was requested. Further visits revealed additional faults along the same heating-control path.
Working through the controls
The first return visit replaced the heat sequencer and found that the fan relay also needed replacement. At the next visit, a replacement fan relay allowed the equipment to run when tested at the air handler, but a thermostat fault prevented normal wall-control operation.
A thermostat change restored heat during that visit, although full fan control remained unavailable. The office arranged further attention rather than treating that partial result as the end of the repair.
A later test found a heat-strip breaker fault
At the latest completed assessment, the homeowner reported cold air. Testing found that a failed breaker was energizing only part of the electric heat-strip kit. Our technician replaced that breaker and ran the equipment again.
The final service summary recorded proper operation. This was a sequence of distinct control and power faults, with each return test adding information. The eventual result followed sequencer, relay and breaker work, rather than a single assumed thermostat problem.