Heat was not circulating through this Wallingford home. Testing at the electric air handler found a failed internal relay that was not passing power to the fan when heating was requested. Further visits revealed additional faults along the same heating-control path.

Electric heat controls repair service photo at the Wallingford home
Equipment documented during the Wallingford service visit.

Working through the controls

The first return visit replaced the heat sequencer and found that the fan relay also needed replacement. At the next visit, a replacement fan relay allowed the equipment to run when tested at the air handler, but a thermostat fault prevented normal wall-control operation.

A thermostat change restored heat during that visit, although full fan control remained unavailable. The office arranged further attention rather than treating that partial result as the end of the repair.

A later test found a heat-strip breaker fault

At the latest completed assessment, the homeowner reported cold air. Testing found that a failed breaker was energizing only part of the electric heat-strip kit. Our technician replaced that breaker and ran the equipment again.

The final service summary recorded proper operation. This was a sequence of distinct control and power faults, with each return test adding information. The eventual result followed sequencer, relay and breaker work, rather than a single assumed thermostat problem.