Finding a major refrigerant leak at a View Ridge wall connection
The mini-splits struggled when all three indoor units ran on hot days at this View Ridge home. Earlier checks suggested a refrigerant-circuit problem, but the readily visible connections did not reveal a leak. A more intensive investigation was needed.
Following the piping into the home
We recovered only two pounds three ounces of refrigerant from a system that required eighteen pounds two ounces with its line-set allowance. That large difference confirmed significant refrigerant loss.
The leak search located damaged fittings at an exterior-wall penetration in the backyard. Our technician repaired those connections, then performed pressure and vacuum checks before adding refrigerant again.
Testing after the circuit was sealed
After the checks showed no additional leakage, the system was recharged and run-tested. The technician recorded normal operation at departure.
This repair gave the original hot-weather complaint a confirmed cause and location. The problem was not simply several rooms demanding cooling at once: the system had lost much of its charge through fittings that required closer access to investigate.