Finding a supply problem before continuing a Shoreline diagnosis
The mini-split at this Shoreline home was not working, but the first issue was outside its refrigerant circuit. Our technician found an improper electrical supply, including a 120-volt reading on one leg and shared circuit connections. Further cooling diagnosis needed to wait until the supply was corrected.
Checking the power available to the equipment
The inspection involved a Daikin system dating from 2014. The electrical findings affected the ability to evaluate its operation, so the visit did not establish a completed repair to the heating and cooling equipment. The photo documents the electrical panel inspected during the assessment.
The recommendation was to involve an electrician to review the circuits and discuss the supply options, including possible subpanel work. Those were proposed next steps for the electrical installation, rather than work completed during this diagnostic appointment.
Defining the next trade and the next test
Once the equipment has a correct supply, additional testing can establish whether any separate cooling fault remains. A replacement option was also discussed, but the original diagnostic visit left the equipment condition unresolved beyond the electrical findings.
For the homeowner, the useful result was knowing where the investigation needed to begin. Replacing a refrigerant part or assuming a failed outdoor unit would not address the supply issue identified during testing. The service plan put the electrical review first, with a return to equipment diagnosis after that prerequisite was handled.