Finding what was damaging the thermostat in Roxhill
The heating and cooling controls were not behaving normally, and replacing the thermostat alone would not have addressed the cause. At this Roxhill home, the diagnostic work traced the problem back to a transformer producing excessive voltage. The return visit focused on correcting that supply before finishing the thermostat installation.
Tracing the control problem upstream
The first visit found a disconnected indoor wire. After it was reconnected, the outdoor unit came on while the indoor equipment did not. Further testing found a shorted thermostat. A separate thermostat was used to check whether the equipment could respond.
Continuing the investigation revealed that the transformer was putting out too much voltage and causing failures in the thermostat controls. That finding changed the repair scope: the power supplying the control had to be addressed as well as the control itself.
Replacing the transformer and finishing the control installation
On the return visit, our technician installed a replacement 40 VA transformer at the indoor unit. We then tested the system and finished installing the new thermostat. The equipment turned on as expected before departure.
For the homeowner, this was a repair aimed at the reason the controls were failing, rather than another isolated thermostat change. The service photo shows the transformer and its wiring inside the equipment. The completed work joined the diagnosis, corrected supply and thermostat installation in one tested control system.