Finding two tubing kinks before replacing a pump in North Beacon Hill

A slow condensate pump does not always mean the pump itself has failed. At this North Beacon Hill home, Evergreen followed the water path before deciding what needed correction.

Heating and cooling equipment from the North Beacon Hill maintenance visit
Equipment from the North Beacon Hill service visit.

The maintenance work

The Mitsubishi air handler’s pump ran for more than a minute while struggling to discharge water. The technician found two kinks in its vinyl tubing, corrected them and cleaned the pump. Water then moved normally. Pump replacement was still recommended because the motor had been working against that restriction.

The drain pan was cleaned and treated, and the outdoor coil was cleaned. Refrigerant and electrical connections were acceptable. A blinking MHK2 thermostat also received attention: batteries were replaced, and the technician noted a stored low-battery code consistent with the timing of the reported blinking.

Continuing system care

The system was operating well after the corrections. The visit completed the tubing adjustment, pump cleaning and battery change, while leaving pump replacement as a separate recommendation rather than assuming the original slow discharge required immediate replacement.