A small drain pump brings a Normandy Park furnace to a stop
A furnace problem can begin with the water it produces rather than the heat it makes. At this Normandy Park home, a failed condensate pump was allowing its reservoir to fill and engage the overflow safety switch, stopping the system.
Following the water to the shutdown
During the initial January visit, our technician inspected the condensate line and found no ice or blockage at that time. Testing pointed to the pump itself. A replacement was needed, so the first visit ended with a temporary drainage arrangement and a return repair to schedule.
That distinction mattered: the diagnosis identified the failed component, but the permanent repair still depended on installing and testing the new pump. The technician also considered whether an earlier frozen line might have contributed, without presenting that possibility as a confirmed cause.
Replacing the pump and checking the furnace
On the return visit, we installed the new condensate pump and tested water flow. The technician noticed the blower rattling against the pump and added rubber pads. Heating and drainage were working during the final checks.
The visit also included furnace maintenance, filter cleaning, burner inspection and electrical checks. We replaced the hot surface igniter and tested heating and airflow. Dirt in the blower wheel remained a recommendation for a separate pull-and-clean visit.
The completed work addressed the pump failure and included an operating check of the furnace. It also left a clear distinction between the repairs performed that day and the deeper blower cleaning still recommended for future care.