Finding why a Lower Queen Anne furnace shut down
The furnace was not turning on, and its E04 warning showed that a safety had tripped. At this Lower Queen Anne home, the important question was why the shutdown had happened. Our technician continued beyond the warning to check combustion settings and the condition of the burners.
Checking pressures and burner condition
The 40,000-BTU American Standard furnace had gas pressure set too high in both heating stages. Our technician adjusted both stages and inspected the burners, which were heavily corroded. The burners and their channels were cleaned, and replacement was recommended because of their condition.
The inspection also checked other parts of the startup and air-moving system. Inducer and blower amperage were good. The igniter and flame rod had been replaced the previous year and still appeared in good condition; the flame rod was cleaned during this visit.
Testing the adjustments and planning burner work
Temperature rise in both first- and second-stage heating was within manufacturer specifications during the operating checks. Those tests provided a check on the adjustments completed that day.
The corroded burners remained a separate concern. A distributor reported the part discontinued, so additional manufacturer sourcing was still needed. For the homeowner, the visit addressed the pressure settings and cleaning while making clear why the burner recommendation remained on the plan. Annual maintenance was also recommended. The service photo shows the furnace opened during the assessment.