Locating a line-set leak in a Lawton Park mini-split
A Lawton Park mini-split needed a dedicated refrigerant investigation after an earlier visit found no refrigerant in the system. That first assessment had raised concerns about the outdoor equipment's operation. The next appointment focused on isolating the refrigerant circuits and locating the loss.
Checking the proprietary connections
Our technician spoke with technical support to confirm that pressure testing through this MrCool system's proprietary line-set connections was feasible. We disconnected the indoor zones from the outdoor unit and tested them separately, narrowing the investigation to an individual circuit.
Testing identified a leak in the suction line serving the main living-area head, connected to the outdoor unit's C port. The technician also observed discolored oil residue with a burned odor. That observation raised concern about possible contamination inside the indoor equipment and existing line sets.
Repair options, with the system still off
An acid flush of the indoor units and existing line sets was recommended to address that concern before returning the outdoor equipment to service. Options for the leaking line were discussed with the homeowner, who planned to contact the office about further work.
The system remained inoperable at the end of this appointment. No leaking connection was recorded as repaired during the leak search. A later job was scheduled, but the available history does not establish its completion or a restored operating result. The completed contribution was a more specific leak location and a documented contamination concern, giving the next repair decision information that the initial low-refrigerant finding alone could not provide.