Following water damage to refrigerant and control repairs in Burien
A water-damaged indoor control board stopped this Burien system. Replacing the board was only part of the response: further inspection found a failed refrigerant metering valve and ice buildup associated with the water problem.
Checking beyond the damaged board
The earlier assessment found a blower that would not run and corrosion around the control connection. Our technician replaced the board, then investigated where the water had come from.
The indoor expansion valve, or TXV, was identified as failed. The outdoor capacitor was also outside its specified range, and the outdoor board had burned resistors. The heat pump was left off until further repairs could be completed.
Completing the additional repairs
A later completed visit replaced the TXV, defrost board, capacitor and filter drier. The system was pressure-tested, evacuated and charged to the manufacturer's specification.
An operating test confirmed a twenty-one-degree air-temperature difference. Later maintenance records also describe functioning equipment. The repair therefore followed the damage back to additional faults, rather than treating the new indoor board as the entire solution.