A low-refrigerant warning and weak temperature output brought us to this Bryant home. A refrigerant investigation confirmed a charge shortfall and multiple faulty fittings, with further repair needed after the initial search.

Multi-zone refrigerant and control repair service photo at the Bryant home
Equipment documented during the Bryant service visit.

Repairing the refrigerant connections

The first leak-search visit found the system three and a half pounds short. Because parts and time were needed, the remaining repair was rescheduled rather than reported as completed that day.

A later visit repaired multiple fittings, pressure- and vacuum-tested the circuit, recharged it and checked operation. Some piping insulation still needed a return visit.

Following the remaining upstairs problem

The homeowner then reported shutdown and poor upstairs cooling. A subsequent assessment restored power to an unplugged condensate pump and worked with technical support to identify a branch-box fault.

The upstairs circuit was moved to another port on the branch box, after which cooling was recorded as proper. The history shows why the final answer involved refrigerant connections, a pump-power correction and zone distribution. It preserves the remaining insulation work as unfinished rather than folding it into the successful cooling test.