Finding two refrigerant leaks in a Briarcliff Daikin system
The three-zone Daikin system at this Briarcliff home had no refrigerant when our technician began the leak investigation. The work needed to locate the loss and establish whether the existing equipment could be repaired.
Isolating the leaking sections
We isolated and pressure-tested the system components. Testing found leakage in the kitchen zone and in the outdoor unit. That showed the problem involved more than one part of the refrigerant circuit.
The technician contacted the distributor about the outdoor coil and found that it was no longer available. With a leaking outdoor coil and no replacement part available through that inquiry, the technician could not offer a completed repair of the existing system.
Moving the discussion to replacement
The system remained inoperable at the end of the leak-search visit. We discussed the findings with the homeowner and arranged for a comfort advisor to follow up about equipment replacement.
The useful answer was the combination of test results and parts availability. Adding refrigerant would not address two identified leaks, and a proposed coil repair depended on a part that could not be obtained. The appointment established why replacement needed to be considered; it did not establish that a new system had already been installed.