Following a blower-control repair through ignition testing in Bothell
The indoor blower would not run in cooling at this Bothell home. Testing found that the control board was not sending its run signal. The visit developed into control work, cleaning and a return check of the furnace ignition circuit.
Control work and an unfinished first test
The homeowner approved same-day work after the initial checks. Coil cleaning was also performed. During the repair, a fuse opened and further ignition difficulties meant the work could not be completed on that first attempt.
The technician recorded the need for a return visit rather than reporting the system as fully repaired. On return, the fuse was replaced and ignition testing continued.
Correcting the flame-sensor connection
The remaining fault was traced to the flame-sensor connection. Wiring was moved from the multi-pin connector to the independent flame-sensor terminal.
The furnace then began heating properly, and the technician recorded the work as complete. This sequence shows the useful role of testing after control work: the final heating result followed the wiring correction, rather than being assumed from the initial board-related repair.
Need help with your heating system?
Tell us what the equipment is doing and when the problem appears.
