Following a blower-control repair through ignition testing in Bothell

The indoor blower would not run in cooling at this Bothell home. Testing found that the control board was not sending its run signal. The visit developed into control work, cleaning and a return check of the furnace ignition circuit.

Furnace control and ignition repair service photo at the Bothell home
Equipment documented during the Bothell service visit.

Control work and an unfinished first test

The homeowner approved same-day work after the initial checks. Coil cleaning was also performed. During the repair, a fuse opened and further ignition difficulties meant the work could not be completed on that first attempt.

The technician recorded the need for a return visit rather than reporting the system as fully repaired. On return, the fuse was replaced and ignition testing continued.

Correcting the flame-sensor connection

The remaining fault was traced to the flame-sensor connection. Wiring was moved from the multi-pin connector to the independent flame-sensor terminal.

The furnace then began heating properly, and the technician recorded the work as complete. This sequence shows the useful role of testing after control work: the final heating result followed the wiring correction, rather than being assumed from the initial board-related repair.